Brand Name : TC
Model Number : TRM060/20
Place of Origin : China
Range of Power : 20-200 kVA
Operating Methods : 3 in 3 out, online double conversion
Input Power Factor : > 0.99
Output Power Factor : 0.9
Input Frequency : 50/60 Hz
Output Rated Frequency : 50/60 Hz
Protection Rating : IP20
Communication Interface : RS232, RS485, dry contacts, SNMP cards (option), emergency shutdown
Product Application
TRM series modular UPS power, the industry leading, all-digital power distribution product, collects the most advanced technology in power electronics and automatic control, thus resulting in breakthrough improvements in power reliability, availability and maintainability of the critical equipment.
It integrates the technical features of traditional tower-type with the need of modern modular server rooms, ensuring modular design together with high reliability of the system.
It is widely used in government, finance, communications, education, transportation, meteorology, radio and television, industrial and commercial taxation, health care, energy and electricity and other sectors.
Range of Power / Working Methods
20-200 kVA, 3 in 3 out, online double conversion
Product Features
Model | TRM 060/20 |
TRM 120/20 |
TRM 200/20 |
|
Capacity | 60kVA | 120kVA | 200kVA | |
Main Input | Terminal Connection | three phase + N + PE | ||
Input Voltage | 380/400/415VAC (Line-Line) | |||
Input Frequency | 50/60Hz | |||
Power Factor | >0.99 | |||
Current Distortion Rate | THDi<3% (100% linear load) | |||
Range of Voltage | 304-478Vac (Line-Line) at full load; 304V-228Vac (Line-Line) linear derating from 100% to 75% | |||
Frequency of Voltage | 40-70Hz | |||
Battery | Voltage of Battery | ±240VDC (32-44 cells adjustable) | ||
Charging Power | 20%* Active power | |||
Charging Voltage Accuracy | ±1% | |||
Bypass | Voltage of Bypass | 380V/400V/415V (Line-Line) | ||
Range of Voltage | -20% - +15% | |||
Frequency Range of Bypass | 50/60Hz (rated frequency) ±1Hz, ±3Hz, ±5Hz | |||
Output | Rated Output Voltage | 380/400/415VAC (Line-Line) | ||
Rated Frequency | 50/60Hz | |||
Output Power Factor | 0.9 | |||
Voltage Accuracy | ±1.0% | |||
Output Dynamic Response | <5% (20%-80%-20% load step) | |||
Dynamic Recovery Time | <20ms (0%-100%-0% load step) | |||
Output Total Harmonic Distortion | <1% (linear load) , <5.5% (nonlinear load) | |||
Inverter Overload | 110% transfer to bypass after 1 hour; 125% transfer to bypass after 10 minutes; 150% transfer to bypass after 1 minute; > 150% transfer to bypass after 200 ms |
|||
Frequency Accuracy | 0.10% | |||
Range of Tracking | Adjustable, ±0.5Hz-±5Hz, Default ±3Hz | |||
Speed of Tracking | Adjustable, 0.5Hz/S-±3Hz/S, Default 0.5Hz/S | |||
Peak Ratio | 3:01 | |||
Three-Phase Accuracy | 120°±0.5° | |||
System | Efficiency | Normal mode:95% Economic mode:99% | ||
Battery Mode | 95% | |||
Screen | LCD+LED, touchscreen + keyboard | |||
Protection Rating | IP20 | |||
Communication Interface | RS232, RS485, dry contacts, SNMP cards, generator interface | |||
Working Environment | 0-40℃ (working temperature) ; -25℃~70℃ (storage temperature) ; 0-95% (no condensation) | |||
Noise (dB) / m | <66dB | |||
Options | SNMP cards, lightning protection, battery temperature compensation, SMS alarm, dust net, dual input unit, seismic assembly | |||
Type of Cabinet | 3-modular cabinet | 6-modular cabinet | 10-modular cabinet | |
Size (W*D*H) (mm) | Main Body | 600*900*1100 | 600*900*1600 | 600*900*2000 |
TCPM20 Module | 440*590*134 | |||
Weight (kg) | Main Body (with modules) | 171kg | 277kg | 399kg |
TCPM20 Module | 22kg |
![]() |